kVA to Amperage Calculator

Convert kilovolt-amperes (kVA) to amperes (A) for single-phase and three-phase electrical systems. Also shows real power and wire sizing recommendations.

LINE CURRENT
--
Real Power (kW)
--
Reactive Power (kVAR)
--
Wire Size (AWG)
--
Breaker Size (A)
--

kVA to Amps Conversion

Converting kVA to amperes is one of the most common calculations in electrical engineering and is essential for properly sizing conductors, breakers, and protective devices. The conversion depends on whether the system is single-phase or three-phase, and requires knowing the system voltage.

Electrical equipment such as transformers, generators, and UPS systems are typically rated in kVA. However, wire sizing, fuse selection, and circuit breaker ratings are based on current in amperes. Accurately converting between these units ensures safe and code-compliant electrical installations.

Conversion Formulas

Single Phase: I = (kVA × 1000) / V
Three Phase: I = (kVA × 1000) / (V × √3)

Where I is current in amperes, kVA is apparent power in kilovolt-amperes, V is line voltage (line-to-line for 3-phase), and sqrt(3) approximately equals 1.732.

Quick Reference Table (3-Phase)

kVA208V240V480V600V
1541.6 A36.1 A18.0 A14.4 A
3083.3 A72.2 A36.1 A28.9 A
50138.8 A120.3 A60.1 A48.1 A
75208.2 A180.4 A90.2 A72.2 A
100277.6 A240.6 A120.3 A96.2 A
5001388 A1203 A601 A481 A

Wire Sizing Guide

  • Up to 20 A: 12 AWG copper (20A breaker)
  • 21-30 A: 10 AWG copper (30A breaker)
  • 31-60 A: 6 AWG copper (60A breaker)
  • 61-100 A: 3 AWG copper (100A breaker)
  • 101-200 A: 3/0 AWG copper (200A breaker)
  • Always verify with NEC tables and local codes for specific installation conditions.

Frequently Asked Questions

Why is sqrt(3) used for three-phase calculations?

In a balanced three-phase system, the three voltage phases are 120 degrees apart. The relationship between line voltage and phase voltage involves sqrt(3) = 1.732. This factor appears because power in a three-phase system is the sum of power in three single-phase circuits, and the vector relationship between line and phase quantities introduces the sqrt(3) factor.

Should I use line-to-line or line-to-neutral voltage?

For three-phase calculations, always use line-to-line voltage (e.g., 480V, not 277V). For single-phase calculations, use the voltage at which the load operates. In a 480V three-phase system, single-phase loads between a line and neutral operate at 277V.

How do I account for derating and safety margins?

The NEC requires that conductors be sized for 125% of the continuous load current. For example, if your calculated current is 80A, you need conductors rated for at least 100A. Additionally, apply derating factors for ambient temperature, conduit fill, and altitude as required by NEC Article 310.